Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T18CM07233
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/27/2018 | FRAMING | Approved | ||
11/21/2018 | FRAMING | Not ready for Inspection | ||
11/16/2018 | FRAMING | Denied | 1) Seal 2 car Garage front chases. 2) Block combustion and relief vents. 3) Replace damaged H2O heater B-vent. 4) Correct swaled top plates above cut studs at garage relief vents. 5) West entry top plates need fire foam. 6) Rebuild Tub diverter wall in east hall bath. 7) Move N. Kitchen counter GFCI to window stud. 8) S.E. Bedroom- staple romex out of box. 9) Fire foam N. Kitchen & S.E. bedroom top plates. 10) Secure Master BR. 4 gang switch box. 11) Move PEX from master shower can light, need 12" clearance. 12) Master BR. ABS needs FHA & stud shoe. 13) Laundry recept needs to be tied into circuit. 14) Nail off dryer FHA strap. |