Permit: T18CM07232

Parcel: 112040340


Addresses:

2626 E FLORENCE DR


Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T18CM07232

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
10/15/2019 EXT METAL CLIPS/EXT SHEATHING Approved Work is covered; no visible violations.
09/12/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval main house only.
05/22/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval Shear nailing is good, however roof framing does not match approved plans. Trusses have been replaced by I-joists, which are not shown on plans. Also, center area shows existing 6 in 12 Pitch, that has new I-joists installed at approximately 1/2 in 12 pitch. There are parapet walls not shown on plans. Lastly, joist hangers have no nails into joists; install nails or provide manufacturers installation instructions showing these are not needed.
05/15/2019 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection No plans on site