Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 10/15/2019 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
Work is covered; no visible violations. |
| 09/12/2019 |
EXT METAL CLIPS/EXT SHEATHING |
|
Partial Approval |
main house only. |
| 05/22/2019 |
EXT METAL CLIPS/EXT SHEATHING |
|
Partial Approval |
Shear nailing is good, however roof framing does not match approved plans. Trusses have been replaced by I-joists, which are not shown on plans. Also, center area shows existing 6 in 12 Pitch, that has new I-joists installed at approximately 1/2 in 12 pitch. There are parapet walls not shown on plans. Lastly, joist hangers have no nails into joists; install nails or provide manufacturers installation instructions showing these are not needed. |
| 05/15/2019 |
EXT METAL CLIPS/EXT SHEATHING |
|
Not ready for Inspection |
No plans on site |