Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T18CM07226
Inspection Description - FRAMING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/02/2019 | FRAMING | Approved | ||
| 06/05/2019 | FRAMING | Denied | Exterior walls to be elevated 6” above finished floor per details 1/A5.1, 3/A5.1& 2/A5.1. Finished floor and existing floor same elevation not per plan. Modifications required to a ensure moisture does not enter addition | |
| 05/23/2019 | FRAMING | Not ready for Inspection | 1-Tub not installed per previous corrections. 2-Heating unit not roughed in.3 -Washer standpipe is less than 18". 4-Water heater is not located per plans, and is in the required clear space for the water closet. 5-Kitchen sink and circuit are not shown on approved plans. 6-Smoke detector not installed. 7-Neutrals and grounds not separated at sub-panel. Inspection stopped. |
|
| 05/16/2019 | FRAMING | Correction Required | Have all intermediates ready for this inspection. Plumbing, mechanical, electrical, and framing. Tub/ shower must be in and full of water and allfixture plumbing with VTR and full of water for test. Sub panel and all bonding, grounding, feeders and branch circuits. Heat source and all rough shall be installed. Water heater rough and hot/cold lines to be installed. Install all windows per plan. Recall all required inspections when ready. |
|
| 12/17/2018 | FRAMING | Partial Approval | CHANGED FROM AP TO PA BY BSTEVENS TO ALLOW FOR ADDITIONAL INSPECTIONS |