Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T18CM06824
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/06/2019 | FIRE - ALARM FINAL | Approved | ||
11/27/2019 | FIRE - ALARM FINAL | Partial Approval | Acceptance test conducted. Elevator in compliance. List of outstanding items: -Obtain permit for monitoring. -Need as builts approved and all fees paid. -Provide locking/secure box around transformer plug from teleguard communicator to outlet. -Tamper switch on 2nd floor reporting as water flow. This was resolved and retested while on site. -Work room on plans wants horn/strobe in center of room. -Replace strobe only in NE office with horn/strobe as indicated on plans. -Need to test comm failures. -Provide record of completion. -Update TFD fire dispatch phone number with central station. -Two way communication on 3rd floor not working. |
|
10/11/2019 | FIRE - ALARM FINAL | Partial Approval | See T19FC00199 for notes |