Inspection Status: Denied
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/07/2018 | ELECTRIC - SERVICE UPGRADE | Denied | Provide access Permit is for unit#1 only does not match scope of work 4 meter pack installed with subpanels Ground verified Bond gas and water lines Riser to be installed level Expose underground conduit for inspection All subpanels to be grounded separate buildings Next denial may result in a refee |
|
| 09/07/2018 | ELECTRIC - SERVICE UPGRADE | Approved | Detailed list left with contractor for final inspection requirements | |
| 09/06/2018 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : There is no access to the site.| 920 * |
|
| 09/06/2018 | ELECTRIC - SERVICE UPGRADE | Denied | underground electric installed without inspection not to proper depth. |