Permit: T18CM06712

Parcel: 10709033B


Addresses:

444 W ALTURAS ST

Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Date Description Inspector Results Comments
01/15/2020 REINFORCED MASONRY PRE-GROUT Approved
01/07/2020 REINFORCED MASONRY PRE-GROUT Denied Wall is already grouted, anchor bolts for ledger board are recessed to far into the wall to attach a ledger board.
12/06/2019 REINFORCED MASONRY PRE-GROUT Partial Approval Missing anchor bolts 32" O.C. per detail #3. Missing horizontal joint re-inforcement 16" O.C. per detail #2.
Beam saddles appear to be misaligned.
Re-inspection fee applies.
12/05/2019 REINFORCED MASONRY PRE-GROUT Denied Called phone number listed 2 times, 1113 am, 1140 am. Knocked on door, young lady answered said she didn’t live there and had no plans. Recall.
11/22/2019 REINFORCED MASONRY PRE-GROUT Partial Approval Bond beam ok
Need anchor bolts for ledger inspected before grout.
11/19/2019 REINFORCED MASONRY PRE-GROUT Partial Approval Ok to grout west block door wall and SE column.

Have east block wall plan revised to show change from flat roof to gable roof and the new rebar and anchor bolt requirements for this change.
11/14/2019 REINFORCED MASONRY PRE-GROUT Partial Approval Ok to grout 1st lift