Permit: T18CM06695

Parcel: 14101006C

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T18CM06695

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/29/2018 PLUMBING - INTERMEDIATE Approved
10/26/2018 PLUMBING - INTERMEDIATE Denied 1- Shall provide approved strap for the condensate drains.
2- The first floor soil stack clean out is located behind the water closet. Shall provide 18 inchest of frontal clearance.
3- Clothes washer overflow drain is incomplete.
4- Shall provide a water test on the gray water piping.
5- Shall remove the test cap on the unused 3 inch riser located at the front of garage and provide a perm cap