Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T18CM06695
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/29/2018 | PLUMBING - INTERMEDIATE | Approved | ||
10/26/2018 | PLUMBING - INTERMEDIATE | Denied | 1- Shall provide approved strap for the condensate drains. 2- The first floor soil stack clean out is located behind the water closet. Shall provide 18 inchest of frontal clearance. 3- Clothes washer overflow drain is incomplete. 4- Shall provide a water test on the gray water piping. 5- Shall remove the test cap on the unused 3 inch riser located at the front of garage and provide a perm cap |