Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/07/2018 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
| 09/05/2018 | PLUMBING - GAS PRESSURE TEST | Partial Approval | 1. 1 1/4 GAS PIPE ON WEST SIDE OF HOUSE NEEDS TO BE SECURED WITH UNISTRUT TO HOUSE. MAY NEED TO MOVE PIPE CLOSER TO THE HOUSE. 2. PIPE ON ROOF SHOULD HAVE A CONNECTION POINT ON THE ROOF CHANGE SO IT'S NOT BOWING, WILL ALSO NEED TO BE SECURED WITH APPROVED STRAPS TO BLOCKING. 3. EAST SIDE PIPING WILL NEED AT LEAST ONE STRAP AS WELL. |