Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/20/2019 ELECTRIC - FINAL Approved
01/31/2019 ELECTRIC - FINAL Correction Required Exterior wet/ damp location J Bowes and fixture boxes required at patio and porch.
When flex or any wire used in EMT or flex it must have a W in the write label signifying OK for wet/damp locations.
When using flex in wet or damp locations it requires a drip loop before entering a J or Fixture box.