Inspection Status: Passed
Inspection History: COT - RSBU - Excavation/Rebar/Zoning
| Date |
Description |
Inspector |
Results |
Comments |
| 12/12/2018 |
COT - RSBU - Excavation/Rebar/Zoning |
RCAMACHO |
Approved |
Entered by CBELL1 - |
| 12/11/2018 |
COT - RSBU - Excavation/Rebar/Zoning |
DMCCARTHY |
Approved |
Entered by CBELL1 - for two piers-caisson at the front entry area. Not for main structure addition. |
| 10/29/2018 |
COT - RSBU - Excavation/Rebar/Zoning |
RCAMACHO |
Denied |
Entered by CBELL1 - Missing f-2 footers south garage wall
Missing holddowns south garage wall
Except f-2footers south deck |
| 10/26/2018 |
COT - RSBU - Excavation/Rebar/Zoning |
ESTEVENS |
Denied |
Entered by CBELL1 - 3 inch clearance required from rebar to earth. Center footing is two, F-2 footings. Rebar is required at corners |