Permit: T18CM06233

Parcel: 11627544B

Inspection Status: Passed

Inspection History: COT - LCBU - Framing

Permit Number - T18CM06233

Inspection Description - COT - LCBU - Framing

Inspection Status - Passed

Date Description Inspector Results Comments
02/11/2019 COT - LCBU - Framing TVALENCIA Approved Entered by CBELL1 -
02/08/2019 COT - LCBU - Framing TVALENCIA Not ready for Inspection Entered by CBELL1 - Work is incomplete
02/07/2019 COT - LCBU - Framing TVALENCIA Denied Entered by CBELL1 - 1- Shall seal all top plate penetrations with fire rated foam or caulk. 2- Shall provide blocking at all horizontal sanitary vents every 5 feet. 3- Shall provide (3) sided blocking at all forced air vents.
12/20/2018 COT - LCBU - Framing DMCCARTHY Not ready for Inspection Entered by CBELL1 - Required inspections still need before 1035 Framing can be signed off. Required inspections still need before 1035 Framing can be signed off. 2035 electric intermediate 3035 plumbing intermediate All trades complete inside wall and floor diaphragm. Then framing inspection, 1035. 1035, 2035, 3035, all at the same