Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/12/2018 | FRAMING | Approved | DID NOT HAVE VISUAL ON 2ND LIFT, BUT OK TO PROCEED. | |
| 10/11/2018 | FRAMING | Partial Approval | Corrections dated 10-3-18 ok, resolve 01020 prior to approving 01035 | |
| 10/03/2018 | FRAMING | Correction Required | Repair and fix the Lintel that is falling apart above the front ext window opening. strap all plate breaks together to make on solid wall. Owner is Jose @ 1 (520) 464-9033 Apply Copper Napthanate to Rim joist contacting top of Masonry exterior wall as it is untreated wood in direct contact with masonry that will absorb water in wet times. Install corner studs for drwall backing. Install stud under top plate plate break. No anodized drywall screws are permitted for framing and attaching. Bolt 90' corvers or wall ends to the masonry for required support of the interior wood framed 2x4 shell. |
|
| 09/11/2018 | FRAMING | Denied | provide treated sill plate, prove that provide anchor bolts or pins every four feet and within 12” of ends. | |
| 09/11/2018 | FRAMING | Denied | work incomplete provide treated sill plate, prove that provide anchor bolts or pins every four feet and within 12” of ends. |