Permit: T18CM06134

Parcel: 11308269B


Addresses:

910 E HEDRICK DR

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
04/04/2019 PLUMBING - FINAL Approved
04/03/2019 PLUMBING - FINAL Denied 1- Shall provide a water hammer arrestor on the dishwasher supply line.
2- Shall secure the dishwasher drain hose as high as possible to the bottom of counter top.
3- Condensate drain has back pitch at branch tail piece connection.
4- Address not posted on house.
5- Shall provide locking refrigerant port caps on condenser.
6- Water Heater T & P drain shall terminate 6 inches above sub grade.
2nd floor showers incomplete.
7- Shall paint all sanitary vents through roof.
04/02/2019 PLUMBING - FINAL Denied Install appliances, missing water hammer arrestors, GFCI in downstairs bath will not reset, disconnect for HVAC is behind the unit, home is still being worked on. stopped inspection. Call when home is finished.