Permit: T18CM06134

Parcel: 11308269B


Addresses:

910 E HEDRICK DR

Inspection Status: Not ready for Inspection

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
02/01/2019 PLUMBING - INTERMEDIATE Not ready for Inspection Gates locked, no one on site, no access
02/01/2019 PLUMBING - INTERMEDIATE Approved Second attempt, owner there. Inspection complete and approved
01/31/2019 PLUMBING - INTERMEDIATE Correction Required Second floor venting not per code. See notes from January 30, 2019 inspection
01/30/2019 PLUMBING - INTERMEDIATE Denied 1- Shall provide a 2 inch waste line for the clothes washer gray water waste line.
2- Shall install all second floor waste and soil lines as per the approved plans or Chapter 9 2012 IPC.
3- Shall provide non corrosion screws for securing the closet flanges.
4- Re test the DEV system.
01/28/2019 PLUMBING - INTERMEDIATE Cancelled
01/25/2019 PLUMBING - INTERMEDIATE Partial Approval need to seal all pipe penetrations through bottom plate of wall rodent proofing with an approved product for example mortar
Furthermore framing was approved already but should’ve only been inspected at the same time as MEP
Customer agreed to call all MEP‘s and framing at same time