Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/04/2019 | BUILDING - FINAL | Approved | ||
| 04/03/2019 | BUILDING - FINAL | Denied | 1- Shall provide a water hammer arrestor on the dishwasher supply line. 2- Shall secure the dishwasher drain hose as high as possible to the bottom of counter top. 3- Condensate drain has back pitch at branch tail piece connection. 4- Address not posted on house. 5- Shall provide locking refrigerant port caps on condenser. 6- Water Heater T & P drain shall terminate 6 inches above sub grade. 2nd floor showers incomplete. 7- Shall paint all sanitary vents through roof. |