Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/16/2018 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 08/14/2018 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999 #8 ROMEX FROM ROOF WILL NEED CONDUCTORS PROTECTED WHERE THEY ENTER ELECTRICAL LOAD CENTER. PROVIDE PROOF OF 2 GROUND RODS ATTACHED WITH #4CU. WATER AND GAS BONDS REQUIRE GOOD CONDUCTION SO PLEASE REMOVE PAINT, WHERE ATTACHED TO PIPES. SMOKE DETECTORS ARE REQUIRED IN EACH SLEEPING ROOM AND HALLWAY. * |
|
| 08/10/2018 | ELECTRIC - SERVICE UPGRADE | Correction Required | 1.) 2 ground rods required or expose existing rods. old/existing #4 connected to unknown 2.) Gas Bond required 3.) Label all breakers in service panel |