Permit: T18CM06085

Parcel: 117081180


Addresses:

827 S 8TH AV #03

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
04/19/2019 PLUMBING - INTERMEDIATE Approved still need to figure out a way to secure the closet flanges. Also recommend putting some kind of dry pack or slurry mix under the tub as it’s floating 3 inches above the floor
04/18/2019 PLUMBING - INTERMEDIATE Denied 1- Shall provide (3) sided blocking on forced air vent.
2- Can not have two traps on one trap arm. Shall provide a drain for one lavatory then wet vent the second lavatory.
3- Shall provide Sanitary Tees not Combination Tee Wyes on a vertical position to pick up the fixture trap arms.
4. Shall secure the closet rings to the floor.
5- Shall provide a minimum of 18 inches of copper to the pex adapter fitting at water heater supply lines.
04/17/2019 PLUMBING - INTERMEDIATE Not ready for Inspection work is not complete, too many items to list.
04/15/2019 PLUMBING - INTERMEDIATE Partial Approval Gas, DWV, and water piping test only.
1-Kitchen clean out needs to extend outside of lath.
2-Kitchen vent horizontal offset is not six inches above flood level rim.
3-Provide test for roof leaders