Permit: T18CM06085

Parcel: 117081180


Addresses:

827 S 8TH AV #03

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
04/19/2019 FRAMING Approved
04/18/2019 FRAMING Denied 1- Shall provide (3) sided blocking on forced air vent.
2- Can not have two traps on one trap arm. Shall provide a drain for one lavatory then wet vent the second lavatory.
3- Shall provide Sanitary Tees not Combination Tee Wyes on a vertical position to pick up the fixture trap arms.
4. Shall secure the closet rings to the floor.
5- Shall provide a minimum of 18 inches of copper to the pex adapter fitting at water heater supply lines.
04/17/2019 FRAMING Not ready for Inspection work is not complete, too many items to list.
04/15/2019 FRAMING Correction Required 1-Complete all walls/backing, etc.
2-Complete and seal all fire blocking
03/11/2019 FRAMING Cancelled