Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T18CM05888
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/29/2019 | MECHANICAL - INTERMEDIATE | Approved | ||
05/24/2019 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | The previous correction still needs to be addressed, the soffit that is built as a chase around the mechanical ductwork is not structurally sound. There are sections more than 20 feet that are unsupported. Either the architect needs to provide a detail that the contractor can build off of that is structurally sound, or the contractor can draw up a plan on how he plans on making it structurally sound and have it stamped by a plan reviewer at the city. | |
05/22/2019 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | he main ductwork was framed in with a wood soffit chase. This soffit does not look structurally sound as it sagging off the walls. According to the detail on the plans it should have been built in metal studs. This may need engineering or design team approval, or build per plans. |