Permit: T18CM05888

Parcel: 11618434A

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T18CM05888

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/29/2019 MECHANICAL - INTERMEDIATE Approved
05/24/2019 MECHANICAL - INTERMEDIATE Not ready for Inspection The previous correction still needs to be addressed, the soffit that is built as a chase around the mechanical ductwork is not structurally sound. There are sections more than 20 feet that are unsupported. Either the architect needs to provide a detail that the contractor can build off of that is structurally sound, or the contractor can draw up a plan on how he plans on making it structurally sound and have it stamped by a plan reviewer at the city.
05/22/2019 MECHANICAL - INTERMEDIATE Not ready for Inspection he main ductwork was framed in with a wood soffit chase. This soffit does not look structurally sound as it sagging off the walls. According to the detail on the plans it should have been built in metal studs. This may need engineering or design team approval, or build per plans.