Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T18CM05888
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/22/2019 | BUILDING - FINAL | Approved | SPECIAL INSPECTIONS CERT SENT TO RECORDS | |
10/03/2019 | BUILDING - FINAL | Partial Approval | PLEASE SUBMIT YOUR SPECIAL INSPECTION REPORTS PRIOR TO BUILDING FINAL. THANK YOU | |
09/13/2019 | BUILDING - FINAL | Partial Approval | REVIEW OF AIR BALANCE REPORT COMPLETED. PENDING ENGINEERING FINAL | |
09/05/2019 | BUILDING - FINAL | Partial Approval | PENDING ENGEN FINAL ,MECH FINAL | |
08/29/2019 | BUILDING - FINAL | Denied | 1- Shall provide a mixing valve at both accessible Lavatories. 2- Shall locate the mirror in the west restroom 40 inches max to he reflection of mirror. 3- Shall caulk the Drinking Fountain. 4- Shall provide 90 degree elbow and terminate the condensate drain 6 inches above sub grade. 5- Shall provide address on bldg. 6- GFI outlets not working in restrooms and at Lounge Sink. 7- Shall provide accessible signage at Restrooms. |