Permit: T18CM05888

Parcel: 11618434A

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T18CM05888

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/22/2019 BUILDING - FINAL Approved SPECIAL INSPECTIONS CERT SENT TO RECORDS
10/03/2019 BUILDING - FINAL Partial Approval PLEASE SUBMIT YOUR SPECIAL INSPECTION REPORTS PRIOR TO BUILDING FINAL. THANK YOU
09/13/2019 BUILDING - FINAL Partial Approval REVIEW OF AIR BALANCE REPORT COMPLETED. PENDING ENGINEERING FINAL
09/05/2019 BUILDING - FINAL Partial Approval PENDING ENGEN FINAL ,MECH FINAL
08/29/2019 BUILDING - FINAL Denied 1- Shall provide a mixing valve at both accessible Lavatories.
2- Shall locate the mirror in the west restroom 40 inches max to he reflection of mirror.
3- Shall caulk the Drinking Fountain.
4- Shall provide 90 degree elbow and terminate the condensate drain 6 inches above sub grade.
5- Shall provide address on bldg.
6- GFI outlets not working in restrooms and at Lounge Sink.
7- Shall provide accessible signage at Restrooms.