Permit: T18CM05791

Parcel: 136390800


Addresses:

4749 S LANTANA CI

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/06/2018 ELECTRIC - INTERMEDIATE Approved
07/31/2018 ELECTRIC - INTERMEDIATE Correction Required GFCI for second (new additional bathroom). GFCI's can share a dedicated GFCI circuit for bathrooms. but cannot share the circuit for a bathroom that has a seperate circit that provides GFCI, fan, and lighting load for that original bath. In other words the new bath will need its own general 20 amp circuit for all the loads within that new bathroom and the GFCI can be on that dedicated second bathroom circuit.