Permit: T18CM05701

Parcel: 140420740


Addresses:

7250 S TUCSON BL


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T18CM05701

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/21/2019 PLUMBING - INTERMEDIATE Approved
10/17/2019 PLUMBING - INTERMEDIATE Denied 1- Shall provide a water head test on the system.
10/09/2019 PLUMBING - INTERMEDIATE Partial Approval OK to cover
10/07/2019 PLUMBING - INTERMEDIATE Partial Approval 1- DWV system and overhead and in wall domestic water distribution is okay to cover.
2- This inspection is for Area 2 and 7.
10/03/2019 PLUMBING - INTERMEDIATE Denied 1- There was no contact number or message giving and could not find anyone on site.
09/25/2019 PLUMBING - INTERMEDIATE Partial Approval 1- DWV water test on Sanitary system provide.
2- Overhead and in wall domestic water distribution is okay.
3- Closet flange okay.
09/24/2019 PLUMBING - INTERMEDIATE Denied 1- Shall locate the outlet of the vent to the lavatory located in Area 3 above the crown of trap weir.
2- Lavatory horizontal vent shall be located a minimum of 6 inches above the flood level rim of lavatory.
3- Shall provide a brass DWV male adapter on lavatory trap arm.
4- Domestic water line in wall is missing unistrut clamps.
08/27/2019 PLUMBING - INTERMEDIATE Partial Approval phase 1 ok
08/19/2019 PLUMBING - INTERMEDIATE Partial Approval east family restroom ok
08/07/2019 PLUMBING - INTERMEDIATE Partial Approval OK in areas 1 and 7