Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/19/2018 | PLUMBING - INTERMEDIATE | Approved | ||
| 10/18/2018 | PLUMBING - INTERMEDIATE | Denied | 1- Shall provide a DWV water test on the entire system. 2- Shall secure the closet ring to the floor. 3- Shall provide 11/4 inch water supply to the water heater. 4- Shall relocate the water lines no closer than 12 inches from can light in first floor bathroom. |