Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/15/2019 | PLUMBING - INTERMEDIATE | Approved | ||
| 07/12/2019 | PLUMBING - INTERMEDIATE | Correction Required | Fixture plumbing on most fixtures need horizontal venting in wall to be 6" above the flood rim of the bowl it serves. Clothes washer, S trap, discussed the fix |
|
| 07/10/2019 | PLUMBING - INTERMEDIATE | Denied | DWV system not to code or plan. Nail protect throughout. Leaks at DWV potable water ok. Provide for future solar. Comply with ADA entry | |
| 07/08/2019 | PLUMBING - INTERMEDIATE | Not ready for Inspection | Canceled by contractor. |