Inspection Status: Approved
Inspection History: PLUMBING - ROOF DRAINS
| Date |
Description |
Inspector |
Results |
Comments |
| 08/21/2019 |
PLUMBING - ROOF DRAINS |
|
Approved |
overflows continue to fail test at bottom 90. Please add additional support at the top of those 90s so this won’t continue to happen. |
| 08/20/2019 |
PLUMBING - ROOF DRAINS |
|
Partial Approval |
All roof drains and over flows on west side of building under test and approved except for the over flow drains at the following locations Grids F/5, F/7, F/9, and F/15. These over flows will need to be retested and inspected |
| 06/10/2019 |
PLUMBING - ROOF DRAINS |
|
Partial Approval |
Completion of 10 foot head tests only all drains. Ok to backfill for concrete pour. Recall at completion of tie ins with new test. |
| 06/06/2019 |
PLUMBING - ROOF DRAINS |
|
Not ready for Inspection |
not one set of roof drains is complete and under test from finish floor through roof. |
| 06/05/2019 |
PLUMBING - ROOF DRAINS |
|
Partial Approval |
3 roof drains stating at northwest going south and 4 roof drains starting at southeast corner going north, under test up from ground to 1st connection above wall openings. |