Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T18CM05380

Parcel: 12801005H

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
10/17/2022 FIRE - FINAL Approved
10/10/2018 FIRE - FINAL Partial Approval Good for TCO. Waiting on mall alarm system to be updated.
09/28/2018 FIRE - FINAL Denied All ceiling tiles not in place. Electrical panel not labeled. wall plate on light switch missing. Shall have an extinguisher for B occupancy.