Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/27/2018 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 07/24/2018 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999 1- SHALL INSTALL AND LOCATE ALL GRAB BARS PER DETAIL D-1 A1.1 2- SHALL LOCATE THE WATER CLOSET IN THE MENBS RESTROOM 16 TO 18 INCHES SIDE WALL CLEARANCE. 3- SHALL PROVIDE APPROVED PROTECTION WRAP FOR BOTH LAVATORY P-TRAPS AND SUPPLIES. 4- SHALL PR4OVIDE OPEN FRON SEATS AND ELEONGATED WATER CLOSETS. 5- SHALL PROVIDE MIXING VALVES FOR BOTH LAVATORIES. 6- SHALL LOCATE THE MIRROR IN THE MENS ROOM 40 INCHES AFF. 7- SHALL PROVIDE ACCESSIBLE SIGNAGE AT BOTH MENS AND WOMENS RESTROOMS. 8- SHALL PROVIDE WATER CLOSET FLUSH HANDLES TO THE OPEN SIDE OF ROOM. 9- THE GFCI RECEPTICAL IN THE WOMENS RESTROOM IS NOT WORKING. 10- SHALL PROVIDE TILE OR FRP ON MASONARY WALL AS PER PLAN. * |