Permit: T18CM05239

Parcel: 120087420


Addresses:

732 W OKLAHOMA ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
12/05/2018 MECHANICAL - FINAL Approved still need to fix white wire for neutral only, bushing needed at disconnect, need 90 degree at end of condensate line.
11/30/2018 MECHANICAL - FINAL Partial Approval previous corrections still need to be fixed. White wire for neutral only. Bushing needed at disconnect. Unit data plate not identified. Condensate needs to be properly terminated, 6in above grade and secured.
07/13/2018 MECHANICAL - FINAL Denied 1- white wire for neutral only
2- bushing at disconnect
3- unit data plate not identified
4- condensate not properly terminated
5- condensate not properly supported above roof
6- condensate not coated for U.V. protection
7- all PVC joints to have purple primer prior to glue
8- provide approved truss load calcs as this is not a replacment
9- another failed inspection will result in a re-fee
07/10/2018 MECHANICAL - FINAL Cancelled