Permit: T18CM05211

Parcel: 115211520

Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Permit Number - T18CM05211

Inspection Description - MECHANICAL - HOODS

Inspection Status - Approved

Date Description Inspector Results Comments
02/25/2019 MECHANICAL - HOODS Approved
01/28/2019 MECHANICAL - HOODS Denied I- Shall provide a GFCI receptacle at the mop sink.
2- Shall caulk all fixtures.
3- Shall provide a vacuum breaker on the Ice Machine and Pasta Cooker supply line.
4- Shall post the unit number on the door or space.
5- Shall expose the water heater in the ceiling.
6- Shall provide a indirect waste line for each compartment at the triple compartment sink.
7- Shall label the automatic gas shut off valve on ceiling tile.
12/06/2018 MECHANICAL - HOODS Not ready for Inspection talked to client they will reschedule
12/04/2018 MECHANICAL - HOODS Cancelled Canceled by contractor
11/27/2018 MECHANICAL - HOODS Partial Approval Smoke test ok.