Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/05/2019 | ELECTRIC - FINAL | Approved | ||
| 03/04/2019 | ELECTRIC - FINAL | Correction Required | 1-Aluminum conductor in panel is missing antioxidant at bussing. 2-Irrigation circuit is over fused. |