Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CONSTRUCTION POWER
Permit Number - T18CM05137
Inspection Description - ELECTRIC - CONSTRUCTION POWER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/21/2019 | ELECTRIC - CONSTRUCTION POWER | Approved | Clearance TEP eco | |
08/26/2019 | ELECTRIC - CONSTRUCTION POWER | Denied | 1. Addresses on panels do not match addresses on permit. 2. Install an appropriate size lug to the ground bar and land all the strands to that lug. 3. There are no feeder wires to the west panel, #2. 4. Install anti oxidant paste on aluminum feeds. 5. Missing dead front screws in panel #1. |