Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T18CM05034
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/30/2018 | MECHANICAL - INTERMEDIATE | Approved | ||
11/29/2018 | MECHANICAL - INTERMEDIATE | Partial Approval | B-vent at water heater not properly supported. Provide minimum opening at water heater combustion air intake. Provide full radius bends at flex duct. Flex duct damged. Frame boot boxes 3 sides |