Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/11/2018 | ELECTRIC - SERVICE UPGRADE | Approved | For Final Must see #4 GEC And #4 water/Gas bonds as req by NEC Will also see labeled breakers |
|
| 12/07/2018 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | 1. Provide 2 points of attachment to structure of riser. 2. A/C condenser to be moved from in front of panel or relocate panel. 3. Provide bonding of gas and water. |