Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T18CM04964

Parcel: 133090560


Addresses:

7930 E MABEL DR

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
12/11/2018 ELECTRIC - SERVICE UPGRADE Approved For Final
Must see #4 GEC And #4 water/Gas bonds as req by NEC
Will also see labeled breakers
12/07/2018 ELECTRIC - SERVICE UPGRADE Not ready for Inspection 1. Provide 2 points of attachment to structure of riser.
2. A/C condenser to be moved from in front of panel or relocate panel.
3. Provide bonding of gas and water.