Permit: T18CM04964

Parcel: 133090560


Addresses:

7930 E MABEL DR

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
12/11/2018 ELECTRIC - UNDERGROUND Approved New 400 amp service will supply 200 amp subpanel at shop.
12/07/2018 ELECTRIC - UNDERGROUND Not ready for Inspection 1. Provide 2 points of attachment to structure of riser.
2. A/C condenser to be moved from in front of panel or relocate panel.
3. Provide bonding of gas and water.