Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/22/2018 | PLUMBING - FINAL | Approved | W?H vent corrected, Gas Line at exterior painted. GWest 6-22-2018 | |
| 06/22/2018 | PLUMBING - FINAL | Approved | ||
| 06/21/2018 | PLUMBING - FINAL | Partial Approval | GAT Approved 6-21-2018. Corrections for water heater:No screws allowed in B-Vent other than Vent connector to B-Vent. No B-Vent to B-Vent connection screws! Clearance to combustibles per manufacturer is 1", OSB and any wood within that required inch must be corrected. Paint the exterior exposed black iron gas piping. |