Permit: T18CM04628

Parcel: 129011430


Addresses:

2419 E EASTLAND ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/30/2018 ELECTRIC - FINAL Approved INCR ok to clear.
10/22/2018 ELECTRIC - FINAL Correction Required Show 2 ground rods and clamps and gas bond. If water line all copper and used as the ground then a supplemental rod within5 feet is required. Need to see the sub panel and label
10/15/2018 ELECTRIC - FINAL Correction Required provide gas bond for panel