Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T18CM04624
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/13/2018 | PLUMBING - INTERMEDIATE | Approved | ||
11/27/2018 | PLUMBING - INTERMEDIATE | Correction Required | Permanent cap required on washer behind shower. Install closet flange and shower pan for inspection 11/2” recent at left of water closet must be level or run up hill to 2” vent pipe. |