Permit: T18CM04547

Parcel: 134234150

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T18CM04547

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/16/2018 PLUMBING - INTERMEDIATE Approved
08/08/2018 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*INSTALL PLATE STRAPS WHERE WASTE GOES THROUGH METAL STUDS SEND PICTURES.
07/30/2018 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999
1- SHALL PROVIDE APPROVED MATERIAL FOR THE SANITARY VENT IN CEILING DUE TO PLENUM RATING.
2- SHALL PROVIDE SHIELD PLATES FOR THE 2 INCH HORIZONTAL DRAIN IN WALL.
3- SHALL PROVIDE A RISER CLAMP FOR THE 2 INCH WASTE LINE THRU FLOOR.
4- SHALL PROVIDE DOUBLE FIXTURE FITTINGS FOR THE BACK TO BACK SINKS.
5- RE TEST THE DWV SYSTEM.

*