Permit: T18CM04531

Parcel: 117121900

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T18CM04531

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/22/2019 MECHANICAL - FINAL Approved
12/12/2018 MECHANICAL - FINAL Denied AIR BALANCE SHOWS FC-5.1 HAS NO OUTSID AIR AND EF-5.1 IS NOT MOVING THE SPECIFIED QUANTITY OF AIR.
12/05/2018 MECHANICAL - FINAL Partial Approval Pending air balance report approval.
12/03/2018 MECHANICAL - FINAL Cancelled Cancelled