Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T18CM04291
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/17/2019 | PLUMBING - GAS PRESSURE TEST | Approved | Clear gas meter | |
| 09/16/2019 | PLUMBING - GAS PRESSURE TEST | Cancelled | IVRS - AP canceled | |
| 09/13/2019 | PLUMBING - GAS PRESSURE TEST | Denied | 1- Shall provide a permanent cap on the gas valve outlet fo the dryer supply. 2- Shall remove the plastic around the water heater flu vent and provide a minimum of 1 inch annular space around he B- Vent as requested from the previous inspection. |
|
| 09/12/2019 | PLUMBING - GAS PRESSURE TEST | Cancelled | IVRS - AP canceled | |
| 09/11/2019 | PLUMBING - GAS PRESSURE TEST | Denied | 1- Shall provide a permanent cap on the gas valve outlet fo the dryer supply. 2- Shall remove the plastic around the water heater flu vent and provide a minimum of 1 inch annular space around he B- Vent. |
|
| 09/09/2019 | PLUMBING - GAS PRESSURE TEST | Cancelled | IVRS - AP canceled | |
| 09/06/2019 | PLUMBING - GAS PRESSURE TEST | Denied | Won’t hold pressure. | |
| 09/05/2019 | PLUMBING - GAS PRESSURE TEST | Partial Approval | PARTIALED FOR GAS CLEARANCE | |
| 02/26/2019 | PLUMBING - GAS PRESSURE TEST | Approved |