Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T18CM04238
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/24/2018 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
08/22/2018 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999 1- SHALL PROVIDE A WATER TEST ON THE DWV SYSTEM. 2- SHALL PROVIDE THE MINIMUM TRAP ARM DISTANCE FOR THE CLOTHES WASHER TRAP ARM. 3- SHALL PROVIDE A SHIELD PLATE FOR THE 11/2 VENT AT SOLE PLATE. 4- PLANS CALL OUT FOR A 2 INCH VTR FOR THE 2ND FLOOR WATER CLOSET. 5- 11/2 VENT FOR THE 2ND FLOOR WATER CLOSET RUNS HORIZONTAL BELOW THE FLOOD LEVEL RIM OF THE FIXTURE. * |