Permit: T18CM04228

Parcel: 141094400


Addresses:

6389 E KOUFAX LN


Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T18CM04228

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
08/16/2018 EXT METAL CLIPS/EXT SHEATHING Approved
08/02/2018 EXT METAL CLIPS/EXT SHEATHING Partial Approval 1. GABLE BRACING NEEDS TO BE PER DETAIL, INCLUDING CLIPS AND SPACING.
2. BIRD BLOCKING NEEDS TO BE PER DETAIL, INCLUDING CLIPS IF IT CALLS FOR THEM.
3. FRONT PATIO HAS 4BY6 POSTS, DRAWINGS CALL FOR 6BY6 POSTS, PLEASE ADDRESS. CONNECTION AT 4 BY 10 POST TO BEAM THERE IS NO DETAIL. EITHER NEEDS TO BE LAGGED OR NEEDS PROPER CLIPS HOLDING THAT CONNECTION TOGETHER.
4. SLIDING DOOR HEADER APPEARS TO BE MISSING TRIMMER STUDS.