Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/04/2018 | PLUMBING - GAS PRESSURE TEST | Approved | clear sw gas | |
| 05/29/2018 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | ||
| 05/29/2018 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | ||
| 05/29/2018 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999 1- SHALL PROVIDE APPROVED TWO HOLE STRAPS FOR STRAPPING OF THE GAS LINE. 2- SHALL EXTEND THE WATER HEATER AND WALL HEATER 3- FEET ABOVE THE COOLER WHEN LOCATED WITHIN 10 FEET OF THE COOLER. 3- SHALL PROVIDE DOUBLE WALL FLU VENT AND CAP FOR THE WATER HEATER FLU VENT. 4- SHALL PROVIDE POSITIVE PITCH ON THE T & P DRAIN LINE AND REMOVE THE FLEX LINE. 5- SHALL PROVIDE A SEDIMENT TRAP AT THE WATER HEATER. * |