Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/10/2018 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/08/2018 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1- ALL PLUMBING CORRECTIONS HAVE BEEN MADE. 2- SHALL PROVIDE (3) SIDED BLOCKING ON FORCED AIR VENT IN ENTRY HALL WAY AS REQUESTED. 3- SHALL RELOCATE THE DOMESTIC WATER LINES NO CLOSER THAN 12 INCHES FROM CAN LIGHT IN DINING ROOM. |
|
| 08/07/2018 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999 1- SHALL PROVIDE A WATER TEST ON THE DWV SYSTEM. 2- SHALL MAKE CORRECTIONS FROM PREVIOUS INSPECTION ON 08/06/18 * |
|
| 08/06/2018 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999 1- 2ND FLOOR TUB TRAP ARM DISTANCE DOES NOT MEET THE MINIMUM TRAP ARM DISTANCE OF (2) TIMES THE PIPE SIZE. 2- 2ND FLOOR GARDEN TUB AND SHOWER HORIZONTAL VENT SHALL RISE VERTICALLY 6 INCHES ABOVE THE FLOOD LEVEL RIM OF THE TUB. * |