Permit: T18CM03887

Parcel: 125121730


Addresses:

3441 E 3RD ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/24/2020 ELECTRIC - FINAL Approved RVI
05/17/2019 ELECTRIC - FINAL Correction Required 1-Provide over-current protection for feeders to sub-panel.
2-Separate neutrals from grounds at sub panels.
3-Install all device