Inspection History Details
Inspection Status: Partial Approval
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/07/2018 | FIRE - FINAL | Partial Approval | APPROVED TO OBATAIN TCO FOR OCCUPANCY. Resolve the following items: -repair exit sign above main exit, NW side. -fire alarm needs annual inspection. repair any/all deficiencies noted on report. -alarm was not reporting supervisory signals to central station. -add red lockout to FACP circuit breaker. -repair all deficiencies noted on last annual fire sprinkler inspection report. -mount fire extinguishers for new upstairs classrooms. -bldg referred to general inspector for full inspection. -this is a private school. fire alarm permit needs to be obtained through tucson fire. |
|
| 05/18/2018 | FIRE - FINAL | Prior to Final Inspectn | deferred submittals through the state. charter school. |