Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 09/30/2019 |
ELECTRIC - INTERMEDIATE |
|
Approved |
|
| 09/27/2019 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
Unable to access for inspection. If this inspection does not pass next time, a re-inspection fee will be assessed. |
| 06/17/2019 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
OK to clear electric INCR. still need question answered about the size of the neutral as in previous correction before final. |
| 06/13/2019 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
see previous correction. Specifically the grounding to the new switchgear needs to be addressed before clearance can be turned in. The grounding appears to be too small for the size of the service. Please provide information that it is correct size for that amount of amps. Another failed inspection and no forward progress on this question may result in a reinspection fee. |
| 05/31/2019 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
feeders from switchgear to new 400 amp panel ok. Recommend sending in an RFI as the neutral seems to be too small of gauge. Also where is the grounding for the switchgear? |
| 05/03/2019 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
lunch room, office, tool room, OK to cover |
| 03/20/2019 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
|