Permit: T18CM03449

Parcel: 14021032A


Addresses:

1702 E BANTAM RD


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T18CM03449

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
05/29/2018 ELECTRIC - SERVICE UPGRADE Approved
05/23/2018 ELECTRIC - SERVICE UPGRADE Denied 1 PROVIDE ADDRESS ON PANEL 2 VERIFY GROUND ROD LOCATIONS 3 OPEN ELECTRIC BOX ON WEST SIDE BY LOCK BOX 4 PROVIDE GAS AND WATER BONDS
05/08/2018 ELECTRIC - SERVICE UPGRADE Not ready for Inspection 1- provide clearence at panel
2- provide bond bushing at concentric knock out
3- plug K.O.'s at panel
4- provide blanks at dead front
5- call for electrical reconnect for clearence
6- provide 2 ground rods, 8' in length at 6' apart, #4 wire
7- provide address labe at panel