Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/29/2018 | ELECTRIC - SERVICE UPGRADE | Approved | ||
| 05/23/2018 | ELECTRIC - SERVICE UPGRADE | Denied | 1 PROVIDE ADDRESS ON PANEL 2 VERIFY GROUND ROD LOCATIONS 3 OPEN ELECTRIC BOX ON WEST SIDE BY LOCK BOX 4 PROVIDE GAS AND WATER BONDS | |
| 05/08/2018 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | 1- provide clearence at panel 2- provide bond bushing at concentric knock out 3- plug K.O.'s at panel 4- provide blanks at dead front 5- call for electrical reconnect for clearence 6- provide 2 ground rods, 8' in length at 6' apart, #4 wire 7- provide address labe at panel |