Permit: T18CM03250

Parcel: 136210220


Addresses:

7461 E MARY PL

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
07/26/2018 BUILDING - FINAL Approved
07/16/2018 BUILDING - FINAL Correction Required 2 ground rods required, gas bond and water bond. Electrical contractor needed here to get all panel grounding and bonding straightened out. Keep all Rods and bonding exposed until after inspection so we can find and see all required.
06/19/2018 BUILDING - FINAL Correction Required Electrical service panel is new with seperate old/existing meter socket box. Panel requires-2 Grounding Rods or proof of approved UFER per NEC, Gas bonding and water pipe bonding are required. 36" of clearance required in front of service and solar electrical equipment.