Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T18CM03048

Parcel: 140130160


Addresses:

1941 E BANTAM RD

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/02/2018 MECHANICAL - FINAL Approved
07/18/2018 MECHANICAL - FINAL Not ready for Inspection 1- condensate not properly terminated
2- provide GFCI protected service outlet on roof within 25' of equipment
3- provide access to interior of rooftop duct to verify R-8 (2") duct liner